BTU Calculator
What size air conditioner your room needs — in BTU per hour, from the room itself.
Planning estimate only — not a substitute for a professional Manual J load calculation. Insulation, windows and climate change the real size.
Cooling needed
How it works
Base BTU = room area (sq ft) × 20. Adjust for ceiling: × (ceiling height ÷ 8). Adjust for sun: shady ×0.9, average ×1.0, sunny ×1.1. Add 600 BTU for each person beyond two; add 4,000 BTU if the room is a kitchen. Round up to the nearest common AC size (5,000 / 6,000 / 8,000 / 10,000 / 12,000 / 14,000 / 18,000 / 24,000 BTU). Tonnage = BTU ÷ 12,000.
The formula starts with the floor area: length times width in square feet. Each square foot needs about 20 BTU per hour of cooling in a normally insulated room, so multiplying the area by 20 gives the base load. That base assumes an 8 ft ceiling, so the calculator scales it by ceiling height divided by 8 — a 10 ft ceiling holds a quarter more air, and needs a quarter more cooling. Sun exposure then adjusts the result: a shady room needs 10% less, a sunny room 10% more, because direct sun through windows adds heat all afternoon. People add heat too, so the calculator adds 600 BTU per hour for every person beyond the first two, and a kitchen adds 4,000 BTU for the stove and oven. Finally the total is rounded up to the nearest common air-conditioner size, since ACs are sold in fixed sizes. Tonnage is simply BTU divided by 12,000 — one ton of cooling equals 12,000 BTU per hour.
Worked example: a 12 ft × 15 ft room is 180 sq ft, so the base is 180 × 20 = 3,600 BTU. With an 8 ft ceiling, average sun, 2 people and no kitchen, nothing is added — 3,600 BTU per hour, rounded up to a 5,000 BTU unit (about 0.42 tons). The same room sunny and used as a kitchen needs 3,600 × 1.1 + 4,000 = 7,960 BTU, rounded up to an 8,000 BTU unit.
Second worked example: a 14 ft by 11 ft bedroom in Hyderabad with a 10 ft ceiling, a sunny west-facing window and four people sleeping in it. The area is 154 sq ft, so the base is 154 × 20 = 3,080 BTU. The ceiling adjustment gives 3,080 × (10 ÷ 8) = 3,850 BTU, and sunny exposure takes that to 3,850 × 1.1 = 4,235 BTU. Four people add (4 − 2) × 600 = 1,200 BTU, for a total of 5,435 BTU per hour. The smallest common size covering that is a 6,000 BTU unit — a 0.5 ton air conditioner.
Common mistakes
Three mistakes turn up again and again. The first is measuring the room in metres and entering the numbers as feet, or the other way round — a 4 m by 3 m room is about 13 ft by 10 ft, and entering 4 by 3 as feet gives a load less than a quarter of the real one. Measure in feet, or convert first: multiply metres by 3.28. The second is forgetting the ceiling: Indian bedrooms often have 10 ft ceilings, and skipping that adjustment understates the load by 25%.
The third is buying bigger than the answer on purpose. An oversized unit cools the room in minutes, switches off before it has pulled the humidity out of the air, and leaves the room cold and clammy. Size to the load, round up only to the next common size, and let the unit run steadily.
Frequently asked questions
What is a BTU?
A British Thermal Unit — the heat needed to raise one pound of water by one degree Fahrenheit. An air conditioner’s BTU rating is how much heat it can remove from a room in one hour, so a bigger room needs a higher BTU rating. Indian air conditioners are usually sold by tonnage instead: 1 ton equals 12,000 BTU per hour, so a 1.5 ton AC is an 18,000 BTU unit.
Why 20 BTU per square foot?
It is the standard rule of thumb for a normally insulated room with an 8 ft ceiling, and it matches what most manufacturers use for quick sizing. It is a starting point, not a guarantee — poor insulation, large west-facing windows, a top floor under a hot roof or a humid climate can all push the real number higher, which is why the calculator adjusts for ceiling height, sun and people.
What if my room is bigger than 36,000 BTU?
Above about 36,000 BTU per hour — 3 tons — a single room unit is rarely the answer. One very large unit tends to cool unevenly, leaving far corners warm, and it is noisy. Two smaller units, one over each half of the room, or a ducted system usually cool the space more evenly and give you a backup if one unit fails. The calculator flags this case.
Does ceiling height really matter?
Yes — a 12 ft ceiling holds half as much air again as an 8 ft ceiling, so there is half as much again to cool, and the load rises in proportion. The calculator scales by ceiling height divided by 8, so a 10 ft ceiling adds 25% to the base load. Indian homes often have 10 ft ceilings, so skipping this step is the most common reason a room ends up undersized.
Should I buy bigger than the calculator says?
No — an oversized unit cools the room too fast, switches off before it has dehumidified the air, and leaves the room cold and clammy. It also costs more to buy, uses more electricity on startup, and short-cycling wears the compressor out sooner. Buy the size the load calls for, rounded up only to the nearest common size, and the unit will run steadily and dry the air properly.